ProSight Universal Paperless Recorder: 1–8 Channels, High Accuracy
Universal paperless recorder with up to 8 channels. High accuracy, easy setup, and Modbus communication for monitoring temperature, pressure, flow, vibration, and more.
This universal color paperless recorder is a versatile, high-precision solution for monitoring and recording process parameters across a wide range of industrial applications. Designed for accuracy, ease of use, and universal compatibility, it is ideal for displaying and measuring temperature, humidity, pressure, flow, vibration, and more.
Key Features
-
High Accuracy Measurement: ±(0.2%FS + 1 digit) with clear 3.2’’ TFT color display.
-
Universal Inputs: Supports thermocouples (T.C.), RTDs, mA, and VDC signals.
-
Flexible Channels: Available from 1 up to 8 channels for scalable monitoring.
-
Cold Junction Compensation: Built-in thermocouple compensation for reliable results.
-
Multiple Outputs: 4–20mA, relay, and 24VDC auxiliary power supply options.
-
Industrial Connectivity: RS485 communication with standard MODBUS-RTU protocol, easily integrated with HMI, SCADA, or OPC systems.
-
Advanced Functions: Flow totalization with temperature/pressure compensation, math functions (+, –, ×, ÷, average, max, min).
-
Flexible Display Modes: Curves, bar graphs, and digital displays.
-
Data Management: Powerful PC software for analysis, export to Excel, and printing.
-
Wide Power Range: 100–240VAC operation for industrial environments.
Applications
-
Industrial process monitoring
-
Environmental & building systems
-
Flow and pressure monitoring
-
Vibration and machine diagnostics
-
Laboratory and QA recording
-
Inputs
-
Channels: 1–8 (independent, photoelectric isolation, 400VAC isolation)
-
Input Types: Thermocouple, RTD, mA, VDC, mV, Frequency (0–5kHz)
-
Accuracy: ±(0.2%FS +1 digit)
-
Resolution: 0.1°C (when in temperature mode)
-
Sample Time: 1 sec per 8 channels
-
Decimal: 0–4 programmable
-
Cold Junction Compensation: Built-in (±1°C tolerance)
-
Channel-GND Isolation: 1000VAC
-
Input Impedance:
-
RTD: >20MΩ
-
Thermocouple: >20MΩ
-
4–20mA: 250Ω
-
0–10mA: 500Ω
-
0–5V: 500kΩ
-
1–5V: 500kΩ
-
0–100mV: >20MΩ
-
Supported Sensor Ranges
-
RTD: Pt100 (–200 to 600°C), Cu50/Cu100 (–50 to 150°C)
-
Thermocouples:
-
K: –50 to 1300°C
-
J: 0 to 1000°C
-
T: –200 to 350°C
-
E: 0 to 800°C
-
R/S/B: up to 1700°C
-
N: 0 to 1300°C
-
Memory & Data Handling
-
Capacity: 45 days × record interval × channels
-
Record Interval: 1–3600 seconds (programmable)
-
Memory Type: Built-in flash
-
USB Storage: 8GB (standard), 16GB (optional)
-
File Transfer: All data transferable, .dat format (year/month/day structure)
-
PC Connectivity: USB driver, plug & play
-
Data Export: Excel, curve analysis, print
Display
-
Screen: 3.2’’ Color TFT LCD
-
Resolution: 320 × 240 pixels
-
Display Modes: Digit, curve, bar graph, chart
-
Interval Time: 1–3600 sec (programmable)
-
Backlight Lifespan: 50,000 hours
-
Screensaver: 0–30,000 sec programmable
-
Engineering Units: °C, °F, %, psi, bar, m³/h, ppm, etc.
Outputs (Optional)
-
Relay Outputs: Max 2, programmable
-
Retransmission: Max 2 channels, isolated
-
Auxiliary Power Supply: 24VDC (max 100mA)
-
Communication: RS485 with Modbus-RTU protocol
-
Printer Port: RS232
Functions
-
Flow totalization with temperature & pressure compensation
-
Math functions: +, –, ×, ÷, average, max, min
Power & Construction
-
Supply Voltage: 100–240VAC, 47–63Hz; 24VDC
-
Consumption: Max 20VA (20W)
-
Insulation: >1500VAC to ground/housing
-
Mounting: Panel flush
-
Size / Weight: 96 × 96 × 110 mm; 0.8 kg
-
Working Environment: 0–50°C; 10–85%RH
-
**Order Code: E.g.: MPR800-06 -C1-F-NO-N: universal color paperless recorder, 6 channels, NO, 3A, RS485 communication output, 100-240VAC, Flow totalizer with temperature and pressure compensation, math Function, 100-240VAC, USB data transferring and PC software.Relay output can be as alarm output, also as simple on-off output.Here 1 channel frequency input is included in 16 channels, MPR800 max. 16 channels input. Please advise me the frequency input range or pulse input range when frequency input ordered.
-
-