High-accuracy temperature and humidity transmitter for hazardous areas. Features intrinsically safe and dust explosion-proof options, cast aluminium IP65 housing, and dual LCD display — ideal for natural gas, power plants, and clean room monitoring.

  • The Explosion-Proof Temperature and Humidity Transmitter is a robust and reliable device designed for precise environmental monitoring in hazardous or complex industrial conditions.

    Built with a cast aluminium explosion-proof housing and rated IP65, it ensures safe, stable operation in challenging applications such as natural gas pipeline networks, power plant air systems, and pharmaceutical clean rooms.

    The transmitter utilises imported high-precision temperature and humidity sensors, providing fast response and long-term stability even under fluctuating process conditions. A clear LCD dual display shows both temperature and humidity readings simultaneously for easy on-site monitoring.

    Two intrinsically safe versions are available:

    • Gas Explosion-Proof Model (with display) – suitable for Zone 0, Zone 1, and Zone 2

    • Dust Explosion-Proof Model – suitable for Zone 20, Zone 21, and Zone 22

    Compliant with CE and RoHS standards, this transmitter delivers the reliability, accuracy, and safety required for modern industrial and energy management systems.

    Why Choose This Temperature & Humidity Transmitter
    ✔ Explosion-proof and dust-proof certified for hazardous locations
    ✔ High-precision imported sensors with fast response time
    ✔ Dual LCD display for temperature and humidity values
    ✔ Cast aluminium housing, IP65 protection rating
    ✔ Intrinsically safe design suitable for Zones 0–2 and 20–22
    ✔ Complies with CE and RoHS for industrial safety and quality assurance

  • Intrinsically Safe Temperature and Humidity Transmitter with Probe LFH71
    Relative Humidity

    Sensor

    Digital

    Range 0%~100%RH
    Output 4~20mA(two wire)
    Accuracy ±3%@20°C & 20~80%RH
    Response Time ≤15s (20°C, Slow flow air)

    Relative Temperature

     

    Sensor

    Digital

    Range 0~50°C,-20~60°C etc
    Output 4~20mA(two wire)
    Accuracy ±0.3°C@20'c, For other accuracy, refer to the digital sensor temperature accuracy curve below.

     

     

    The digital sensor temperature accuracy curve

     

     

     

    Intrinsically safe parameters

     

     

    Explosion-proof Marking

    With display: Ex ia IIC T6/T4 Ga

    Without display: Ex ia IIC T6/T4 Ga; Ex ia IIIC T200 85°C/T200 135°C Da 

    Explosion-proof Certificate CE24.2060X
    Intrinsically Safe Parameters

    (RH+、RH-) : Ui : 28VDC; li : 93mA; Pi : 0.65W; Ci : 0.02uF; Li : 0mH

    (T+、T-) : Ui : 28VDC; li : 93mA; Pi : 0.65W; Ci : 0.02uF; Li : 0mH

    Environment Temperature T4 : -40°C~80°C; T6 : -40°C~60°C

     

     

    Other parameters

     

     

    Power Supply 9~28VDC
    Maximum Power 0.04UV (W) (UV=supply voltage)
    Output Load ≤500Ω
    Display

    Intrinsically safe: Optional LCD display (with unit without backlight)

    Dust intrinsically safe: No display

    Housing Material ADC12, stainless steel probe and sintered mesh filter
    Working Temperature T4: -40°C~80°C; T6: -40°C~60°C, 5%~95%RH (non-condensing)
    Protection Class IP65
    Weight ≈666g(Wall-mounted) ≈760g(Duct type) ≈813g(Split type, without accereceries)
    Certificates CE,Intrinsically Safe Explosion-proof, Dust Intrinsically Safe Explosion-proof

     

     

    WARNING

     

    1.The product housing is made of aluminium alloy, please avoid the risk of ignition during use due to impact or friction.

    2. The housing must be reliably grounded during installation.

    3.The product display is made of plastic with a potential danger of electrostatic charge. Please avoid friction during use, or wipe

    with a wet cloth when cleaning.

    4. When the product is used in explosive dust environments, there is a potential danger of electrostatic charge, so it should not

    be used in areas affected by charge-generating processes, mechanical friction, separation processes, electronic emission and

    pneumatic transmission of dust.

     