top of page

Wireless Monitoring for 4–20 mA Instruments Connecting Pressure Level Flow and Analytical Transmitters

Sep 9
10 min read

A plant can have excellent instruments and still poor visibility. A pressure transmitter may be wired correctly, calibrated, and feeding a local controller, yet the data may only be visible in one cabinet, one panel, or one control system. That limits how fast teams can respond to leaks, blocked filters, tank overfills, dosing issues, or process drift.


Wireless monitoring changes that without replacing the field instruments. Existing 4–20 mA pressure, level, flow, and analytical transmitters can often be connected to Monnit analogue-input sensors, then sent wirelessly to a gateway and monitoring platform. The result is wider access to process values, alarm notifications, trend history, and near real-time status from assets that were previously hard to see.


Wide-angle view of a technician checking a 4–20 mA transmitter beside an outdoor process tank
Wireless monitoring can extend visibility from existing field instruments.

Why 4–20 mA instruments are good candidates for wireless monitoring


The 4–20 mA current loop remains one of the most common industrial signalling methods because it is simple, stable, and well suited to long cable runs. A transmitter converts a measured variable into current:


  • 4 mA usually represents the lower range value

  • 20 mA usually represents the upper range value

  • Values below or above that range may indicate a fault, underrange, overrange, or special diagnostic state, depending on the transmitter setup


This applies across many instrument types.


Instrument type

Common measurement

Example wireless use

Pressure transmitter

Pump discharge pressure, filter differential pressure, vessel pressure

Alert when pressure drops, rises, or trends towards a blockage

Level transmitter

Tank level, sump level, silo level

Track inventory or warn before overflow

Flow transmitter

Water, chemical, air, gas, or slurry flow

Detect loss of flow or unexpected consumption

Analytical transmitter

pH, ORP, conductivity, dissolved oxygen, turbidity

Monitor water quality or chemical dosing performance


A Monnit analogue-input sensor acts as a wireless measurement point. It reads the analogue signal, then sends the data by radio to a Monnit gateway. From there, the data can be logged, displayed, and used for alerts.


This approach suits sites that want better visibility but do not want to alter the main control system. It can also help with remote utilities, water and wastewater assets, bulk storage, pump stations, treatment skids, and equipment supplied by third parties.


The main benefits of adding wireless monitoring


Wireless monitoring is not just about removing cable. The larger value comes from making process data easier to reach and easier to act on.


Better access to data


Many 4–20 mA signals terminate in a PLC, local display, chart recorder, or standalone controller. That can be enough for control, but not enough for operations, maintenance, compliance, or management reporting.


Wireless monitoring can make the same measurement visible from a dashboard, mobile device, or central monitoring point. A maintenance lead can see a pump pressure trend without opening a cabinet. An operations team can check tank level before sending a tanker. A utilities manager can review flow patterns across several remote sites.


Near real-time alarms


A local gauge only helps when someone is nearby. Wireless monitoring can send alerts when values pass a threshold, fail to change, move too quickly, or fall outside the expected range.


For example:


  • A falling pressure trend may suggest a pump fault or pipe leak

  • A rising differential pressure may point to a blocked filter

  • A high tank level may require a transfer pump to start

  • A pH value outside limits may call for dosing adjustment

  • A zero flow condition may indicate a closed valve or failed pump


The reporting interval matters. Battery-powered wireless sensors often trade reporting speed against battery life, so “real time” should be set to match the risk. Critical alarms may need short intervals. Slow-changing tank levels can usually report less often.


Lower installation cost on difficult assets


Running new signal cable can be expensive where instruments are far away, buried, elevated, or located across roadways and process areas. Wireless sensors can reduce trenching, conduit, shutdown time, and panel work.


That is especially useful when the goal is monitoring rather than closed-loop control. The control loop can stay as it is, while the wireless sensor provides a parallel visibility layer.


Trend history for maintenance decisions


A single alarm tells a team something has happened. A trend shows how it happened.


Wireless data logging helps reveal patterns such as:


  • Gradual pump wear

  • Seasonal inflow changes

  • Batch-to-batch dosing variation

  • Recurring high-level events

  • Sensor drift or fouling

  • Flow imbalance between lines


These patterns support better maintenance timing and fewer unnecessary site visits.


Close-up view of a 4–20 mA loop wiring diagram beside a wireless analogue input sensor
The integration method depends on how the existing current loop is wired.

How the connection works


A 4–20 mA loop is a series circuit. The same current flows through the transmitter, power supply, and receiving input. That detail matters because a current input cannot simply be connected in parallel like a voltmeter.


There are three common connection cases.


A new monitoring-only loop


If the transmitter is not already connected to a PLC or controller, the Monnit analogue-input sensor can be wired as the receiving input for the loop, provided the sensor type supports 4–20 mA input and the loop has a suitable power supply.


A typical arrangement includes:


  • 24 V DC loop supply, or another supply approved for the transmitter

  • Two-wire or four-wire transmitter

  • Monnit analogue-input sensor set for current input

  • Correct polarity through the loop

  • Suitable enclosure and cable glands for the environment


An existing loop with one receiver


If the transmitter already feeds a PLC or display, the safest design is often to use a signal isolator or current splitter. This device takes the existing 4–20 mA signal and creates a second isolated 4–20 mA output for the wireless sensor.


This avoids several problems:


  • Added loop burden that may exceed the power supply capability

  • Ground loops between systems

  • Unplanned effect on the control input

  • Faults on the monitoring side affecting the control side


Series wiring may be possible in some installations, but it must be checked carefully. Every current input adds resistance, called burden, and the loop power supply must have enough voltage to drive the transmitter plus all input burdens at 20 mA.


A loop with an available retransmission output


Some control equipment, displays, and analytical transmitters provide a retransmitted 4–20 mA output. This is often an ideal source for wireless monitoring because it is already designed to feed another device.


Check whether the retransmitted signal is active or passive, isolated or non-isolated, and scaled the same way as the primary measurement.


Step-by-step integration guide


Use a controlled work process and follow site electrical, instrumentation, and safety procedures. The steps below describe the typical technical path.


1. List the instruments and measurements


Start with a simple register of the transmitters to be monitored.


Record:


  • Tag number

  • Measured variable

  • Range, such as 0 to 1,000 kPa or 0 to 5 m

  • Output signal, normally 4–20 mA

  • Existing receiver, such as PLC, display, recorder, or controller

  • Power supply voltage

  • Hazardous area classification, if relevant

  • Location and enclosure rating


This avoids guesswork later. It also helps decision-makers see which measurements give the best return.


2. Confirm the Monnit sensor input type


Select a Monnit analogue-input sensor that matches the signal. For current loops, use a model or input configuration rated for 4–20 mA current input.


Do not assume a voltage input can read a current loop directly. Some systems use a precision resistor to convert current to voltage, such as 250 ohms to create 1–5 V from 4–20 mA, but this must be designed correctly and allowed for in the loop burden. If a direct 4–20 mA input is available, use it.


3. Choose the integration method


Pick one of these approaches:


Existing situation

Preferred connection method

No existing receiver

Wire the Monnit sensor as the loop receiver

Existing PLC or controller input

Use an isolated signal splitter, or confirm series wiring is acceptable

Available retransmission output

Connect the Monnit sensor to that output

Critical control loop

Use isolation so monitoring cannot disturb control

Hazardous area loop

Use approved barriers, isolators, and equipment for the area


For control or safety-related loops, do not make the wireless sensor a single point of failure.


4. Check loop power and burden


A current loop needs enough voltage to push 20 mA through all devices in series. The transmitter data sheet will state its minimum operating voltage. Each receiving input and barrier adds burden.


The basic check is:


Available loop voltage must exceed transmitter voltage requirement plus all voltage drops at 20 mA.

If the numbers are close, use a signal isolator or a separate output rather than adding another series device.


5. Plan the physical installation


Wireless does not remove the need for good field practice. Place the sensor where it is protected from heat, water ingress, vibration, chemical exposure, and mechanical damage.


Also check radio path to the gateway. Metal tanks, switchrooms, concrete pits, and dense pipework can reduce wireless signal strength. A gateway location with height and fewer obstructions usually performs better.


6. Isolate and wire the signal


Before opening the loop, follow the site isolation process. Confirm whether interrupting the signal will affect control, alarms, or reporting.


For a typical 4–20 mA current input, wire the sensor in the correct polarity according to the Monnit documentation and the loop design. Keep instrument cable screens and earths consistent with site standards. Avoid creating multiple earth points that can lead to noise or ground loop issues.


Label the terminals and update drawings as soon as the work is complete.


Eye-level view of an instrument enclosure with labelled terminal blocks and a wireless monitoring sensor
Good wiring practice protects the existing loop and the new monitoring point.

7. Scale the measurement


The wireless platform needs to convert milliamps into engineering units. Use the transmitter range from the instrument configuration, not only from the nameplate if the device is programmable.


A common linear scaling formula is:


`Measured value = ((mA - 4) / 16) × span + lower range value`


For a pressure transmitter ranged 0 to 1,000 kPa:


  • 4 mA equals 0 kPa

  • 12 mA equals 500 kPa

  • 20 mA equals 1,000 kPa


Analytical transmitters may need extra care. A pH transmitter may be scaled 0 to 14 pH, 2 to 12 pH, or another range chosen for the process. Conductivity and turbidity ranges can vary widely.


8. Set reporting intervals and alarms


Set the reporting interval to match the process speed and risk.


Fast-changing values may need more frequent reporting. Slow tank levels may not. Shorter intervals can reduce battery life, so choose a setting that gives useful visibility without unnecessary transmissions.


Configure alarms for:


  • High and low process values

  • Rate of change where useful

  • No change when change is expected

  • Sensor communication loss

  • Low battery, if battery powered

  • Out-of-range analogue values


Use sensible alarm delays to avoid nuisance alerts from short spikes.


9. Test at known points


Test the full path, not just the wiring.


Use a loop calibrator, transmitter simulator, or controlled process condition to check values near 4 mA, 12 mA, and 20 mA. Confirm that the wireless dashboard shows the correct engineering units and that alarms trigger as expected.


For existing loops, also confirm that the PLC or controller still reads correctly after the monitoring sensor or splitter is installed.


10. Document and hand over


Record the final wiring, scaling, alarm limits, reporting interval, sensor ID, gateway, and battery details. Store this with the instrument loop sheet or asset record.


Good documentation prevents future technicians from removing or bypassing the wireless sensor because it looks unfamiliar.


Common challenges and practical solutions


Challenge

What can go wrong

Practical solution

Loop burden is too high

The transmitter cannot reach 20 mA, or readings clip high

Use an isolated splitter or retransmitted output

Current input connected in parallel

Readings become unstable or incorrect

Wire current inputs in series, or use a splitter

Wrong scaling

Dashboard values look plausible but are wrong

Confirm transmitter range and apply engineering-unit scaling

Poor wireless signal

Missed reports or delayed alarms

Move the gateway, improve line of sight, or use a stronger antenna arrangement where supported

Electrical noise

Readings fluctuate unexpectedly

Check shielding, earthing, cable routing, and isolation

Analytical sensor drift

Wireless data shows a slow error trend

Keep normal calibration and cleaning routines in place

Battery changes too frequent

Maintenance load increases

Adjust reporting interval and alarm settings to suit the process

Hazardous area requirements

Equipment may not be suitable for the location

Use approved barriers, enclosures, and devices rated for the area


The biggest mistake is treating the wireless input as just another pair of wires. It is part of an electrical measurement loop. The original loop function must stay protected.


Where wireless 4–20 mA monitoring works well


Wireless monitoring is a strong fit when the measurement matters, but hardwired integration is too costly or slow.


Good examples include:


  • Remote water tanks and pump stations

  • Chemical bulk storage

  • Filter differential pressure

  • Wastewater lift stations

  • Cooling water flow

  • Boiler feedwater or condensate monitoring

  • Trade waste pH or conductivity

  • Temporary monitoring during commissioning or troubleshooting

  • Legacy panels without modern data access


It also helps when several stakeholders need the same data. Engineering may care about the loop accuracy. Maintenance may care about drift and failure. Operations may care about alarms. Management may care about production loss, water usage, or service response. A wireless monitoring layer can serve all of those needs without forcing every signal into a major control system upgrade.


High-angle view of a remote pump station with wireless monitoring hardware mounted near process piping
Remote assets are often the easiest place to justify wireless monitoring.

Design tips for a reliable installation


A reliable installation starts before anyone lands a screwdriver on a terminal.


Keep these points in mind:


  • Protect the control loop

    If the signal feeds control, dosing, safety interlocks, or compliance reporting, use isolation unless the engineering review confirms another method is safe.


  • Use the right enclosure

    Outdoor installations need suitable IP-rated enclosures, UV-resistant fittings, and cable glands matched to the cable type.


  • Name sensors clearly

    Use plant tags and plain descriptions, such as `PT-204 Filter Outlet Pressure`. Clear names reduce alarm confusion.


  • Avoid alarm overload

    Start with a small number of meaningful alarms. Add more after reviewing trend behaviour.


  • Keep calibration separate from wireless setup

    The wireless sensor reports the signal it receives. It does not fix a poorly calibrated transmitter.


  • Test after any loop change

    A small wiring or scaling change can affect the whole measurement chain.


What success looks like


A successful installation should be almost boring. The existing transmitter still works. The PLC or display still reads correctly. The Monnit analogue-input sensor reports stable values in the right units. Alarms arrive when tested. Trend data builds over time. Technicians can understand the wiring when they open the enclosure later.


That is the real value of adding wireless monitoring to 4–20 mA instruments. It extends the usefulness of pressure, level, flow, and analytical transmitters already installed across the site. It gives decision-makers better access to data, while giving engineers a practical path that respects the original loop design.


Start with one or two high-value measurements, prove the wiring method and reporting setup, then expand to the instruments where visibility will reduce risk, save site visits, or catch faults earlier.


bottom of page